Features
- SmartSequencing™ – SmartSequencing allows bidirectional, safe sequenced power up/down operations via the push of a button or turn of a key.
- Voltage Protection – Extreme Voltage Shutdown (EVS) safeguards from catastrophic under-voltage (under 80V sustained) or over-voltage (over 145V sustained) conditions. The EVS feature can be selectively enabled or disabled according to the preference of the user.
- BlueBOLT Compatible® – IP Control (Telnet or cloud-based BlueBOLT) via SmartSequencing (when connected to CN-1800S/CN-2400S with BB-RS232 Adaptor).
- Diagnostic Lights – Diagnostic lights provide valuable system information including power quality.
- 20 Amp Output Current – 20 amp maximum current capacity.
- DIP Switch Customization – DIP switches and potentiometer allows customization of settings such as sequencing delays, 12V on/off, and more. Security covers are provided to prevent unauthorized personnel from tampering with DIP switches.
Specifications
AC Voltage Input Range 90-139VAC, 50/60Hz
Maximum AC Current Rating 20 Amps (No Breaker)
AC Cord 3/12AWG, 10 feet, black, fixed, NEMA 5-20P plug
AC Receptacles 2 NEMA 5-20R’s (1 duplex)
AC Undervoltage Protection EVS, 77VAC+/-3VAC
AC Overvoltage Protection EVS, 140VAC+/-5VAC
AC Overvoltage Reset Modes Enabled and disabled (configurable via DIP Switch #9)
Operating Temperature Range 5C (40F) to 40C (105F) degrees
Humidity Range <90% rH (Relative Humidity)
Circuit Breaker No Breaker
Front panel diagnostic indicators (LED) Power, Extreme Voltage, Primary Link, Secondary Link
Side Panel DIP Switch Features (with security cover) 1 Minute Delay, 2 Minute Delay, 4 Minute Delay, Force Off NO/NC, 12V Mode On/Off GND Mode On, Momentary/Maintained, Primary/Secondary, EVS Reset Auto/Manual
Side Panel Potentiometer allows fine tune delay adjustments
Remote Terminal +5-30VDC In, 12VDC (12mA) Out
SmartSequencing Phoenix-type 4-Pin Connector, Screw Terminals, Primary & Secondary Links (Current Loop – 1000’ nominal)
Remote Terminal Phoenix-type 5-Pin Connector With Screw Terminals; +12V, STAT, REM, GND, DLY_OUT (Class 1 Wiring)
Force Off Phoenix-type 2-Pin Connector With Screw Terminals, FORCE OFF (Class 1 Wiring)
RS-232 Compatible Yes, indirectly, when connected via SmartSequencing to a Furman Smart Sequencer with an RS-232 port
IP Accessibility Optional IP control via Telnet, HTTP, or BlueBOLT® when used in conjunction with SmartSequencing
Voltmeter Available with SmartSequencing Ethernet option, ± 2VAC accuracy
Ammeter Available with SmartSequencing Ethernet option, ±1A accuracy
Power Consumption (No Load) 10 Watts
Safety Agency CSA, RoHS Compliant